Conference Room


The Conference Room is equipped with audio/visual ammenities with space to accomodate 25+ people for collaborative meetings. Reservations are available free of charge through the Equinix Customer Portal.
HTMLText_28868B4F_263B_2FF4_41BD_BCF27CB5EF6B.html =
Concrete Floor


The main colocation floors are the core of each Equinix IBX data center. Equipment is located in secure private or secure shared environments. Each location provides for robust interconnection among tenants to ensure direct, private exchange of IT traffic with a diverse set of counterparties and providers at distributed IT exchange points inside the carrier-neutral facility.


Most Equinix IBX data centers leverage a multi-tiered overhead cabling system to deliver interconnection solutions throughout the facility.
HTMLText_629B9668_7E0D_EFE3_41B7_914EB6D2F919.html =
Air Handlers
HTMLText_70977347_6F02_3B4F_41CB_E3E96CD61219.html =
Fire Supression Gas Cylinder
HTMLText_7929CC5B_5A68_5966_41C0_CC46E4C1A4AA.html =
Flapper Gate
HTMLText_8F65F99F_985C_35B3_41CE_4A14961E464F.html =
Conference Room


The Conference Room is equipped with audio/visual ammenities for collaborative meetings. Reservations are available free of charge through the Equinix Customer Portal.
HTMLText_9209E433_B9FB_A92B_41D1_F5F8BD957235.html =
Fiber Path


Equinix data centers contain diverse fiber entry points into the building through which our network customers run their fiber.


These diverse fiber paths help to ensure maximum network uptime. In addition, the fiber paths connect this IBX facility to neighboring IBXs, delivering interconnected access between all Equinix customers within the metro area.
HTMLText_9229BD7A_BE2D_9B24_41B1_C06CA14F9D17.html =
Antenna


Many sites are equipped with rooftop areas where customers can install their GPS, line of sight or dish antenna.
HTMLText_9271DB6A_B9E4_9F24_41C2_37F57349907B.html =
Generators
HTMLText_92FD9C5E_BE3B_791D_41E1_A55F5DB052C2.html =
Cooling Units
HTMLText_99CDE0BA_B9DC_A925_41E4_2C84DCD49CC5.html =
Power Panel
HTMLText_9A45032F_BA27_6F3B_41D1_65E288667157.html =
Wi-Fi
HTMLText_9A4D5FF3_BA25_772B_41AC_95542D9A8570.html =
Conference Rooms
HTMLText_9A4F57D7_BA64_976B_41B0_FE34799DD8BD.html =
Mantrap


To reach the data center floor, every Equinix visitor must pass through a series of interlocking doors and travel through a mantrap. The mantrap can only be accessed via two sets of automatic doors, one of which opens to the lobby, the other to the customer circulation area. The doors are made of bulletproof Lexan and are never open at the same time.
HTMLText_9ABD4248_BA5B_A965_41E5_AF06CEA2B2C5.html =
Customer Care


The customer care area is a dedicated space where customers can conduct business or take a break. Conference rooms provide private meeting areas via an online reservation process, free of charge.


A customer break area offers vending machines with coffee and snacks, as well as tables and chairs. Online access is available as are private customer workstations in a convenient, shared work environment. For more information, see the Customer Guide.
HTMLText_9ACE7154_BA3B_EB6D_41C1_DB245266D8CC.html =
Customer Work Stations


Private customer work stations are available in a convenient, shared work environment.
HTMLText_9B084998_BA7D_9BE4_4199_D37330C17940.html =
Our International Business Exchange™ (IBX®) data centers offer 24/7/365 security and customer access, along with a global uptime record of 99.9999%.


Structurally, not all of our facilities are identical—some were built from the ground up while others were acquired or developed in existing spaces.


Equinix is also vendor-neutral, meaning we welcome all service providers inside our data centers, with no preference given to any single vendor. That attracts a broad selection of service providers and their potential partners to our facilities, creating countless opportunities for interconnection. We also offer expert guidance to these companies in order to help them make an informed data center decision.
HTMLText_9B1CB0DF_BA64_E91B_41E0_3581DCC3F9B4.html =
Security Lobby


Within the Security Lobby, visitor identity must be verified with valid government-issued photo identification.


An intrusion detection system monitors all ingress/egress points throughout the facility, while on-premises security personnel physically monitor the facility.
HTMLText_9B599685_BA6C_A9EC_41D4_CC4AF9C1DC4A.html =
Prior to entry into an IBX facility, authorized access is required. Access enrollment types, security profiles and visitor permissions can be managed within the Equinix Customer Portal.


Authorized visitors may use a proxy card with biometric verification for entry into the facility. Authorized access can be set up as permanent permission for 24x7x365 access or with temporary admittance for a specified date/time.
HTMLText_9CF1617A_BA2D_AB25_41E7_220525D0DCEF.html =
IBXflex Office Space


IBXflex® allows customers to build dedicated office or storage space within or near our IBX data centers. IBXflex space comes with 24-hour on-site IBX access, and has the same security, fire suppression and environmental controls as any space inside an Equinix data center.
HTMLText_9CF444EA_B9E5_A925_41E3_48E4A3EE0FF1.html =
Switchgear
HTMLText_9CFA57B8_B9E4_B725_41A2_1D064FC53A38.html =
Uninterruptible Power Supply (UPS)


In order to meet the high uptime requirements for data centers, Uninterruptible Power Supply (UPS) systems are often deployed with redundancy.


Each system of interlocking electrical equipment ensures that continuous power flows to all facility equipment in the case of an outage. The standby UPS systems ensure the seamless transition between grid power, battery backup and generator power in the event of common power problems.
HTMLText_9D014ADD_B9FC_991F_41E6_9E87C69F4E88.html =
Fire Detection and Suppression Systems


Every IBX has a very early smoke detection alarm system, called VESDA for short. The system samples the air at adjustable periods of time, and if the sample is different from a reference sample the machine has taken, an alarm is activated. But water in the dry-pipe system isn’t released until a sprinkler head valve opens, and that requires a temperature of 165 degrees at the sprinkler location. The water is then released only in the area of the fire, and if there’s a false alarm, we have auxiliary drains, so we can safely empty the water out of the facility.
HTMLText_9D4C41DF_B9E4_AB1C_41D8_DD74077B2A0E.html =
Batteries
HTMLText_9D4E65E3_B9FC_AB2B_41DE_8EC4C123302E.html =
Video Surveillance
HTMLText_9D557750_B9FD_B765_41CE_946D7491E5A6.html =
Electrical


Our power systems are designed and managed to perform against rigorous testing and operational processes, with fully documented maintenance procedures at each site.


Equinix engineers also use proprietary automated telemetric systems to continuously monitor all power system components at our data centers, ensuring quick response times and effective support.
HTMLText_9D64A71C_BA25_971D_41DB_DAD7C6F215EC.html =
Raised Floor


The main colocation floors are the core of each Equinix IBX data center. Equipment is located in secure private or secure shared environments. Each location provides for robust interconnection among tenants to ensure direct, private exchange of IT traffic with a diverse set of counterparties and providers at distributed IT exchange points inside the carrier-neutral facility.


Several of our data centers use a traditional “raised floor” system, where the floor panels are removed and cables are snaked in underneath, as opposed to a system where cables are installed overhead.
HTMLText_9DA09F59_BE2C_B766_41B2_5B4587A314CE.html =
Rooftop facilities are critical to IBX operations in many ways. Cooling, antenna locations and other infrastructure contribute to the smooth operation of the building.
HTMLText_9DA2D70F_BA2B_A8FB_41D3_6C6591219877.html =
Operations Center


Our operations center is staffed 24 hours a day to ensure that everything inside the data center is running smoothly. The center monitors the essential systems inside our data centers, including the environment, air flow, power backup and fire suppression.


We also have engineering expertise and subject-matter experts on staff to handle emergency maintenance and preparedness for all key infrastructure components. All of this is tracked from a single, central location and then networked to Equinix headquarters.
HTMLText_9DAC7BBF_BE2C_BF1C_41E0_09FE317FEBC2.html =
Shipping and Receiving


Our IBX Operations staff receives and ships equipment through our loading docks. Customers have the option to get boxes delivered to their cage through our standard Equinix Smart Hands® service, while rack and stack is available through Smart Hands custom ordering.


HTMLText_9DCA3786_BA3B_97ED_41D2_6BC44E752F59.html =
Breakroom


Take a break and unwind. Our customer break areas offer vending machines and kitchen facilities with coffee and snacks, as well as tables, chairs and other amenities.
HTMLText_9DE9D9DB_BA5D_7B64_41D5_D9ADF419E344.html =
Biometric Reader
HTMLText_9DF95BCF_BE2B_BF7B_41C9_63128A2E9038.html =
Cooling Stacks


Maintain suitable environmental conditions for our customer deployments.



HTMLText_9E37D6AB_B9DC_A924_41C2_28F50AB14F27.html =
Overhead Tamper-Proof Cable Tray System and Cable Management
HTMLText_9E50A627_B9ED_A92B_41C9_4772E2E195D5.html =
Secure Cabinet


Individual locked cabinets provide secure, dedicated, space and power capacity within an area shared by multiple Equinix customers. Each secure cabinet includes:


Demarcation point within the cabinet, allowing Equinix to deliver interconnection securely.


Optional cabinet accessories such as cabinet shelves and cable management.


High power-density (upon special approval.)
HTMLText_9E51A1E0_B9DB_AB25_41E2_CAFC50690066.html =
Cage Wall


Built-to-order space based on planned power capacity and cabinet quantity.
HTMLText_9EDAF3A5_B9EF_6F2F_41E1_32840D0E899D.html =
Cabinet Door


Lockable, fully ventilated doors which may be configured for left- or right-window.


Closed 4-post cabinet with adjustable-depth rails.
HTMLText_9F609359_B9EB_AF64_41E2_86D609D82D16.html =
Cage Door
HTMLText_9F8715E4_B9E5_6B2D_41D9_260CCF474A5D.html =
Demarcation Panel


Demarcation points allow Equinix to deliver interconnection to the cage, providing each customer full control over their connections.
HTMLText_B9BFF8BC_8D85_5590_41AF_513D83C0B83E.html =
Conference Rooms
HTMLText_E279BEBA_C124_0CBE_41D7_EE751E10D58D.html =
CRAC Unit
HTMLText_E4F25C6A_D624_87EB_41E2_54D6B5054DAB.html =
Solar Panels
HTMLText_E4FAE233_D65D_8379_41E0_954676D4287F.html =
Diesel Fuel Pumps
HTMLText_E78749AC_D66C_816F_41CC_5FBE5B528DA0.html =
Auto Transfer Switch
HTMLText_FCFAA10F_D664_8129_41C7_5C76B1FB1448.html =
Utility Main Breakers
### Tooltip IconButton_40D1CF05_5278_5B71_41CC_0013BFADF3D9.toolTip = Toggle Gallery IconButton_40D1CF05_5278_5B71_41CC_0013BFADF3D9_mobile.toolTip = Toggle Gallery IconButton_4119B4DD_5188_2E91_41B4_DB380EBC26F2.toolTip = Look Down IconButton_4119B4DD_5188_2E91_41B4_DB380EBC26F2_mobile.toolTip = Look Down IconButton_4185A425_5278_2DB1_41C3_641F043D200A.toolTip = Toggle Fullscreen IconButton_4185A425_5278_2DB1_41C3_641F043D200A_mobile.toolTip = Toggle Fullscreen IconButton_41E822ED_5388_EE8B_41CD_EB27B81427B2.toolTip = Next Panorama IconButton_41E822ED_5388_EE8B_41CD_EB27B81427B2_mobile.toolTip = Next Panorama IconButton_41E842ED_5388_EE8B_41B7_EA16C2B0C826.toolTip = Look Right IconButton_41E842ED_5388_EE8B_41B7_EA16C2B0C826_mobile.toolTip = Look Right IconButton_41E8C2ED_5388_EE8B_41C0_06430D6A3CE9.toolTip = Zoom In IconButton_41E8C2ED_5388_EE8B_41C0_06430D6A3CE9_mobile.toolTip = Zoom In IconButton_41E942E7_5388_EE87_41C9_BDCA41DE74FD.toolTip = Zoom Out IconButton_41E942E7_5388_EE87_41C9_BDCA41DE74FD_mobile.toolTip = Zoom Out IconButton_41E992ED_5388_EE8B_41CD_4C69F9CCA85C.toolTip = Look Up IconButton_41E992ED_5388_EE8B_41CD_4C69F9CCA85C_mobile.toolTip = Look Up IconButton_41E9E2E8_5388_EE89_41CC_948883A3BE45.toolTip = Look Left IconButton_41E9E2E8_5388_EE89_41CC_948883A3BE45_mobile.toolTip = Look Left IconButton_42EB111E_5288_2B89_41D4_AB07275D9789.toolTip = Previous Panorama IconButton_42EB111E_5288_2B89_41D4_AB07275D9789_mobile.toolTip = Previous Panorama Image_4C29BA57_FA27_64A6_41C2_8C6128036ABD.toolTip = Forward Image_4C29BA57_FA27_64A6_41C2_8C6128036ABD_mobile.toolTip = Forward Image_7CBECF07_FA27_9CA7_41D6_2E3CA7A24B44.toolTip = Backward Image_7CBECF07_FA27_9CA7_41D6_2E3CA7A24B44_mobile.toolTip = Backward ## Media ### Title panorama_C62E9834_D624_8F7F_41CF_2891A8BF23FE.label = Security Lobby panorama_C63E57FA_D664_80EB_41A6_9CB9C16E1374.label = Customer Workstations panorama_C77CF1EC_D5E6_5605_41A3_BE598FF42821.label = UPS panorama_C77D3943_D5E6_B603_41B2_3E1E444E1038.label = Colocation Floor panorama_C77D65ED_D5E7_DE07_41D5_3E49A731DD73.label = Breakroom panorama_C77D75FF_D5E6_DE03_41BF_7195FF1E02FE.label = Private Cage panorama_C77D8426_D5E7_FE05_41D1_06CDEE92E592.label = Secure Parking panorama_C77D9F71_D5E7_AA1F_41A8_D66460AD1765.label = Roof panorama_C77DB09F_D5E7_D603_41CF_5A9352252AA9.label = IBX Exterior panorama_C77DFD67_D5E6_6E03_41C8_C6A49C737297.label = Diesel Fuel Pumps panorama_C77F189D_D5E5_F607_41C3_EEF9254B4863.label = Exterior Generators panorama_C77F1B1A_D5E5_AA0D_41D9_C0B3870FC5F3.label = Electrical panorama_C77F3D54_D5E5_AE05_41DA_B87BAC36A6DD.label = Batteries panorama_C77F448F_D5E2_5E03_41CF_6849BB58BD88.label = Generators panorama_C77F8D87_D5E2_AE03_41E2_FC2791454BDB.label = Mantrap panorama_C77FA0C2_D5E2_D67D_41DE_3E8E5DB15F95.label = Utility Main Breakers panorama_C77FBBA0_D5E2_AA3D_41A9_E37A9917B206.label = Conference Room panorama_C77FDEB7_D5E2_EA03_41E2_E9913D087F57.label = Shared Cage panorama_C96085E6_D729_D89E_41D0_988AC5889EC3.label = Shipping and Recieving panorama_CD83AE7B_D779_C876_41C2_AE9DDA8FE8E0.label = Auto Transfer Switch