#: locale=en ## Tour ### Description ### Title tour.name = Atlanta AT1 ## Skin ### Multiline Text HTMLText_0F87460C_267B_FE95_41B3_A209933A58F1.html =
Conference Room


The Conference Room is equipped with audio/visual ammenities with space to accomodate 25+ people for collaborative meetings. Reservations are available free of charge through the Equinix Customer Portal.
HTMLText_14A66AD3_0387_D81F_417F_F0F99907204A.html =
Power Distribution Unit
HTMLText_28868B4F_263B_2FF4_41BD_BCF27CB5EF6B.html =
Concrete Floor


The main colocation floors are the core of each Equinix IBX data center. Equipment is located in secure private or secure shared environments. Each location provides for robust interconnection among tenants to ensure direct, private exchange of IT traffic with a diverse set of counterparties and providers at distributed IT exchange points inside the carrier-neutral facility.


Most Equinix IBX data centers leverage a multi-tiered overhead cabling system to deliver interconnection solutions throughout the facility.
HTMLText_629B9668_7E0D_EFE3_41B7_914EB6D2F919.html =
Air Handlers
HTMLText_70977347_6F02_3B4F_41CB_E3E96CD61219.html =
Fire Supression Gas Cylinder
HTMLText_7929CC5B_5A68_5966_41C0_CC46E4C1A4AA.html =
Flapper Gate
HTMLText_7F600042_2379_989E_41A4_D6231E1355CA.html =
Water Chillers
HTMLText_8F65F99F_985C_35B3_41CE_4A14961E464F.html =
Conference Room


The Conference Room is equipped with audio/visual ammenities for collaborative meetings. Reservations are available free of charge through the Equinix Customer Portal.
HTMLText_9209E433_B9FB_A92B_41D1_F5F8BD957235.html =
Fiber Path


Equinix data centers contain diverse fiber entry points into the building through which our network customers run their fiber.


These diverse fiber paths help to ensure maximum network uptime. In addition, the fiber paths connect this IBX facility to neighboring IBXs, delivering interconnected access between all Equinix customers within the metro area.
HTMLText_9229BD7A_BE2D_9B24_41B1_C06CA14F9D17.html =
Antenna


Many sites are equipped with rooftop areas where customers can install their GPS, line of sight or dish antenna.
HTMLText_9271DB6A_B9E4_9F24_41C2_37F57349907B.html =
Generators
HTMLText_92FD9C5E_BE3B_791D_41E1_A55F5DB052C2.html =
Cooling Units
HTMLText_99CDE0BA_B9DC_A925_41E4_2C84DCD49CC5.html =
Power Panel
HTMLText_9A45032F_BA27_6F3B_41D1_65E288667157.html =
Wi-Fi
HTMLText_9A4D5FF3_BA25_772B_41AC_95542D9A8570.html =
Conference Rooms
HTMLText_9A4F57D7_BA64_976B_41B0_FE34799DD8BD.html =
Mantrap


To reach the data center floor, every Equinix visitor must pass through a series of interlocking doors and travel through a mantrap. The mantrap can only be accessed via two sets of automatic doors, one of which opens to the lobby, the other to the customer circulation area. The doors are made of bulletproof Lexan and are never open at the same time.
HTMLText_9ABD4248_BA5B_A965_41E5_AF06CEA2B2C5.html =
Customer Care


The customer care area is a dedicated space where customers can conduct business or take a break. Conference rooms provide private meeting areas via an online reservation process, free of charge.


A customer break area offers vending machines with coffee and snacks, as well as tables and chairs. Online access is available as are private customer workstations in a convenient, shared work environment. For more information, see the Customer Guide.
HTMLText_9ACE7154_BA3B_EB6D_41C1_DB245266D8CC.html =
Customer Work Stations


Private customer work stations are available in a convenient, shared work environment.
HTMLText_9B084998_BA7D_9BE4_4199_D37330C17940.html =
Our International Business Exchange™ (IBX®) data centers offer 24/7/365 security and customer access, along with a global uptime record of 99.9999%.


Structurally, not all of our facilities are identical—some were built from the ground up while others were acquired or developed in existing spaces.


Equinix is also vendor-neutral, meaning we welcome all service providers inside our data centers, with no preference given to any single vendor. That attracts a broad selection of service providers and their potential partners to our facilities, creating countless opportunities for interconnection. We also offer expert guidance to these companies in order to help them make an informed data center decision.
HTMLText_9B1CB0DF_BA64_E91B_41E0_3581DCC3F9B4.html =
Security Lobby


Within the Security Lobby, visitor identity must be verified with valid government-issued photo identification.


An intrusion detection system monitors all ingress/egress points throughout the facility, while on-premises security personnel physically monitor the facility.
HTMLText_9B599685_BA6C_A9EC_41D4_CC4AF9C1DC4A.html =
Prior to entry into an IBX facility, authorized access is required. Access enrollment types, security profiles and visitor permissions can be managed within the Equinix Customer Portal.


Authorized visitors may use a proxy card with biometric verification for entry into the facility. Authorized access can be set up as permanent permission for 24x7x365 access or with temporary admittance for a specified date/time.
HTMLText_9CF1617A_BA2D_AB25_41E7_220525D0DCEF.html =
IBXflex Office Space


IBXflex® allows customers to build dedicated office or storage space within or near our IBX data centers. IBXflex space comes with 24-hour on-site IBX access, and has the same security, fire suppression and environmental controls as any space inside an Equinix data center.
HTMLText_9CF444EA_B9E5_A925_41E3_48E4A3EE0FF1.html =
Switchgear
HTMLText_9CFA57B8_B9E4_B725_41A2_1D064FC53A38.html =
Uninterruptible Power Supply (UPS)


In order to meet the high uptime requirements for data centers, Uninterruptible Power Supply (UPS) systems are often deployed with redundancy.


Each system of interlocking electrical equipment ensures that continuous power flows to all facility equipment in the case of an outage. The standby UPS systems ensure the seamless transition between grid power, battery backup and generator power in the event of common power problems.
HTMLText_9D014ADD_B9FC_991F_41E6_9E87C69F4E88.html =
Fire Detection and Suppression Systems


Every IBX has a very early smoke detection alarm system, called VESDA for short. The system samples the air at adjustable periods of time, and if the sample is different from a reference sample the machine has taken, an alarm is activated. But water in the dry-pipe system isn’t released until a sprinkler head valve opens, and that requires a temperature of 165 degrees at the sprinkler location. The water is then released only in the area of the fire, and if there’s a false alarm, we have auxiliary drains, so we can safely empty the water out of the facility.
HTMLText_9D4C41DF_B9E4_AB1C_41D8_DD74077B2A0E.html =
Batteries
HTMLText_9D4E65E3_B9FC_AB2B_41DE_8EC4C123302E.html =
Video Surveillance
HTMLText_9D557750_B9FD_B765_41CE_946D7491E5A6.html =
Electrical


Our power systems are designed and managed to perform against rigorous testing and operational processes, with fully documented maintenance procedures at each site.


Equinix engineers also use proprietary automated telemetric systems to continuously monitor all power system components at our data centers, ensuring quick response times and effective support.
HTMLText_9D64A71C_BA25_971D_41DB_DAD7C6F215EC.html =
Raised Floor


The main colocation floors are the core of each Equinix IBX data center. Equipment is located in secure private or secure shared environments. Each location provides for robust interconnection among tenants to ensure direct, private exchange of IT traffic with a diverse set of counterparties and providers at distributed IT exchange points inside the carrier-neutral facility.


Several of our data centers use a traditional “raised floor” system, where the floor panels are removed and cables are snaked in underneath, as opposed to a system where cables are installed overhead.
HTMLText_9DA09F59_BE2C_B766_41B2_5B4587A314CE.html =
Rooftop facilities are critical to IBX operations in many ways. Cooling, antenna locations and other infrastructure contribute to the smooth operation of the building.
HTMLText_9DA2D70F_BA2B_A8FB_41D3_6C6591219877.html =
Operations Center


Our operations center is staffed 24 hours a day to ensure that everything inside the data center is running smoothly. The center monitors the essential systems inside our data centers, including the environment, air flow, power backup and fire suppression.


We also have engineering expertise and subject-matter experts on staff to handle emergency maintenance and preparedness for all key infrastructure components. All of this is tracked from a single, central location and then networked to Equinix headquarters.
HTMLText_9DAC7BBF_BE2C_BF1C_41E0_09FE317FEBC2.html =
Shipping and Receiving


Our IBX Operations staff receives and ships equipment through our loading docks. Customers have the option to get boxes delivered to their cage through our standard Equinix Smart Hands® service, while rack and stack is available through Smart Hands custom ordering.


HTMLText_9DCA3786_BA3B_97ED_41D2_6BC44E752F59.html =
Breakroom


Take a break and unwind. Our customer break areas offer vending machines and kitchen facilities with coffee and snacks, as well as tables, chairs and other amenities.
HTMLText_9DE9D9DB_BA5D_7B64_41D5_D9ADF419E344.html =
Biometric Reader
HTMLText_9DF95BCF_BE2B_BF7B_41C9_63128A2E9038.html =
Cooling Stacks


Maintain suitable environmental conditions for our customer deployments.



HTMLText_9E37D6AB_B9DC_A924_41C2_28F50AB14F27.html =
Overhead Tamper-Proof Cable Tray System and Cable Management
HTMLText_9E50A627_B9ED_A92B_41C9_4772E2E195D5.html =
Secure Cabinet


Individual locked cabinets provide secure, dedicated, space and power capacity within an area shared by multiple Equinix customers. Each secure cabinet includes:


Demarcation point within the cabinet, allowing Equinix to deliver interconnection securely.


Optional cabinet accessories such as cabinet shelves and cable management.


High power-density (upon special approval.)
HTMLText_9E51A1E0_B9DB_AB25_41E2_CAFC50690066.html =
Cage Wall


Built-to-order space based on planned power capacity and cabinet quantity.
HTMLText_9EDAF3A5_B9EF_6F2F_41E1_32840D0E899D.html =
Cabinet Door


Lockable, fully ventilated doors which may be configured for left- or right-window.


Closed 4-post cabinet with adjustable-depth rails.
HTMLText_9F609359_B9EB_AF64_41E2_86D609D82D16.html =
Cage Door
HTMLText_9F8715E4_B9E5_6B2D_41D9_260CCF474A5D.html =
Demarcation Panel


Demarcation points allow Equinix to deliver interconnection to the cage, providing each customer full control over their connections.
HTMLText_B9BFF8BC_8D85_5590_41AF_513D83C0B83E.html =
Conference Rooms
HTMLText_E279BEBA_C124_0CBE_41D7_EE751E10D58D.html =
CRAC Unit
HTMLText_E4F25C6A_D624_87EB_41E2_54D6B5054DAB.html =
Solar Panels
HTMLText_E4FAE233_D65D_8379_41E0_954676D4287F.html =
Diesel Fuel Pumps
HTMLText_E78749AC_D66C_816F_41CC_5FBE5B528DA0.html =
Auto Transfer Switch
HTMLText_FCFAA10F_D664_8129_41C7_5C76B1FB1448.html =
Utility Main Breakers
### Tooltip IconButton_40D1CF05_5278_5B71_41CC_0013BFADF3D9.toolTip = Toggle Gallery IconButton_40D1CF05_5278_5B71_41CC_0013BFADF3D9_mobile.toolTip = Toggle Gallery IconButton_4119B4DD_5188_2E91_41B4_DB380EBC26F2.toolTip = Look Down IconButton_4119B4DD_5188_2E91_41B4_DB380EBC26F2_mobile.toolTip = Look Down IconButton_4185A425_5278_2DB1_41C3_641F043D200A.toolTip = Toggle Fullscreen IconButton_4185A425_5278_2DB1_41C3_641F043D200A_mobile.toolTip = Toggle Fullscreen IconButton_41E822ED_5388_EE8B_41CD_EB27B81427B2.toolTip = Next Panorama IconButton_41E822ED_5388_EE8B_41CD_EB27B81427B2_mobile.toolTip = Next Panorama IconButton_41E842ED_5388_EE8B_41B7_EA16C2B0C826.toolTip = Look Right IconButton_41E842ED_5388_EE8B_41B7_EA16C2B0C826_mobile.toolTip = Look Right IconButton_41E8C2ED_5388_EE8B_41C0_06430D6A3CE9.toolTip = Zoom In IconButton_41E8C2ED_5388_EE8B_41C0_06430D6A3CE9_mobile.toolTip = Zoom In IconButton_41E942E7_5388_EE87_41C9_BDCA41DE74FD.toolTip = Zoom Out IconButton_41E942E7_5388_EE87_41C9_BDCA41DE74FD_mobile.toolTip = Zoom Out IconButton_41E992ED_5388_EE8B_41CD_4C69F9CCA85C.toolTip = Look Up IconButton_41E992ED_5388_EE8B_41CD_4C69F9CCA85C_mobile.toolTip = Look Up IconButton_41E9E2E8_5388_EE89_41CC_948883A3BE45.toolTip = Look Left IconButton_41E9E2E8_5388_EE89_41CC_948883A3BE45_mobile.toolTip = Look Left IconButton_42EB111E_5288_2B89_41D4_AB07275D9789.toolTip = Previous Panorama IconButton_42EB111E_5288_2B89_41D4_AB07275D9789_mobile.toolTip = Previous Panorama Image_4C29BA57_FA27_64A6_41C2_8C6128036ABD.toolTip = Forward Image_4C29BA57_FA27_64A6_41C2_8C6128036ABD_mobile.toolTip = Forward Image_7CBECF07_FA27_9CA7_41D6_2E3CA7A24B44.toolTip = Backward Image_7CBECF07_FA27_9CA7_41D6_2E3CA7A24B44_mobile.toolTip = Backward ## Media ### Title panorama_1404D428_23F9_98EA_4189_0D54BEC75332.label = IBX Exterior panorama_179BD717_23E9_B8A6_41C0_CB30A9C86336.label = Roof panorama_34897F1E_231F_88A6_41AA_4D3B44DB2CCA.label = 3rd Floor Mantrap panorama_37C01862_2318_889E_41B8_CAA4A00883AD.label = Chillers panorama_37C06823_2318_889E_41B7_6201CFC725EA.label = Secure Cabinets panorama_37C08B18_2319_88AA_419D_947698664194.label = 2nd Floor Conference Room panorama_37C0CBB3_2319_8FFE_41A6_BA20797E334C.label = Cooling Tower panorama_37C0EE45_2319_889A_41B3_312058DF02C4.label = 3rd Floor Customer Care panorama_37C42F55_2319_88BA_418F_3517C9909542.label = Diesel Room panorama_37C46533_2318_B8FE_4194_3E7D25B5880D.label = Colocation Floor panorama_37C470BD_2319_99EA_41AA_3FCBC9E0EAAE.label = Electrical Room 2nd Floor panorama_37C496DE_2318_79A6_41B2_F16151F9F04D.label = Building Entry panorama_37C4B11E_231F_B8A6_41B3_52B98ED63E45.label = 5th Floor Generators panorama_37C4B814_231B_88BA_41A9_410280582B3D.label = Power Switchgear Room panorama_37C4BD37_231B_88E6_41B0_628926FC8564.label = Rooftop Generators panorama_37C52C9A_231B_89AE_41BB_1508D3660DE8.label = Security Lobby panorama_37C547A7_231B_87E6_41B5_2D39D3D9AF8C.label = 2nd Floor Colo Mantrap panorama_37C568CE_231B_89A6_41B4_3C965B5300E0.label = Private Cages panorama_37C592CF_2318_99A6_4190_0A6FD15374E3.label = Entrance to 2nd Floor IBX panorama_37C5A70B_2318_98AE_41BE_55F7D82530D4.label = 6th Floor Colo Entrance panorama_37C5B148_2318_98AA_4161_1A3518CF2592.label = Freight Elevator panorama_37C5B349_2318_F8AA_41B0_D4EEAD7EFF1B.label = Private Cage Interior 1 panorama_37C5E288_2318_B9AA_41B4_BA687B9BD1B2.label = Generator Switchgear panorama_37C75D04_2319_889A_41BF_5076C22ABAC5.label = Colocation Entry panorama_37C77D70_2318_8B7A_41B2_A40FED651418.label = Shipping & Recieving panorama_37C77DFD_2318_8B6A_41A3_0478663871C0.label = 2nd Floor Connection Room panorama_37C7B68B_2318_F9AE_4191_7EA1160715FB.label = Secure Cage panorama_37C7D291_2318_79BA_41B8_40EEFCB3BE4B.label = 2nd Floor DC Plant panorama_37C7D3B5_2318_BFFA_41A7_5DCCE4EAB71F.label = 3rd Floor Breakroom panorama_37C7E1E9_231F_9B6A_41B2_5CA239D605EA.label = 3rd Floor UPS Battery Room panorama_6A016ACC_6790_951A_41C6_F3D1236673AF.label = Colocation 3rd Floor panorama_6C65BF8F_2328_87A6_41B3_611620490E95.label = Electrical Room 3rd Floor panorama_7C5E84E0_64C9_0FF4_4189_6E0843370200.label = Colocation 6th Floor panorama_7C7B6E2E_64FF_3A4C_41BB_02E301A05FD2.label = Private Cage 6th Floor panorama_7DCE305B_64C9_06D4_41C4_2967F36BD0BD.label = Private Cage Interior 2 panorama_D54A7E60_472C_91C7_41B1_DFBA8055F623.label = Conference Room 3rd Floor